Minimum horizontal cable bend radius
The minimum bend radius for horizontal
cables will vary depending on the condition of the cable during
installation (tensile load) and after installation when the cable is at
rest (no-load).
Requirements
- The minimum bend radius, under no-load
conditions, for 4-pair UTP cable shall not be less than four times the
cable diameter and the minimum bend radius of 4-pair ScTP cable, under
no-load conditions, shall be eight times the cable diameter.
Minimum backbone cable bend radius
Requirements
- The minimum bend radius, under no-load
conditions, for multipair backbone cable shall be ten times the cable
diameter.
Minimum patch cable bend radius
Requirements
- The minimum bend radius, under no load
conditions, for 4-pair ScTP patch cable shall be eight times the cable
diameter.
NOTE - Minimum bend radius conditions and
cables not specified under subclause 10.2.1 (i.e., Category 6) are under
further study.
Maximum pulling tension
Requirements
- The maximum pulling tension of 4-pair 24
AWG UTP cable shall be 110 N (25 lbf).
- For multipair backbone cable,
manufacturer's pulling tension guidelines shall be followed.
|